Type X-SPOS Multiple Shielded Pairs, Overall Shield Instrumentation Cables

APPLICATIONS:
For analog data circuits where groups within the cable carry different signal strengths, making electrical isolation of shields desirable. Also for digital input or other circuits where electrically isolated pairs are required. For use in free air, raceways or direct burial, wet or dry locations, and permitted for use in Class I Division 2 industrial hazardous locations per NEC.

CONSTRUCTION:
Stranded copper conductors, XLP (Cross-Linked Polyethylene) insulation, black/white or black/red and number-identified conductors, pairs twisted with mylar aluminum polyester tape shield, stranded copper drain wire, overall mylar aluminum polyester tape shield over assembly -100% coverage and stranded copper drain wire, CPE (Chlorinated Polyethylene) jacket overall, surface printed.

STANDARDS:

  • Conductors conform to ASTM B-3 & B-8.
  • Insulation conforms to UL Standard 44.
  • Cables designed to pass the IEEE-383 & IEEE-1202 tests.
  • Jacket suitable for Sunlight Resistant applications.
  • Cables meet requirements of ICEA S-82-552 and ICEA S-73-532.
 

 

NO.OF PAIRS

2

3

4

6

8

12

24

36

50

20 AWG – STRANDED

BASIC CAT. NO.

JACKET mils

O.D. in.

WEIGHT LBS/mft

7-3552

45

.45

65

7-3553

45

.47

90

7-3554

45

.50

115

7-3556

60

.61

168

7-3558

60

.73

194

7-3562

60

.88

285

7-3574

80

1.06

485

7-3586

80

1.21

695

7-3600

80

1.39

890

18 AWG – STRANDED

BASIC CAT. NO.

JACKET mils

O.D. in.

WEIGHT LBS/mft

7-3652

45

.52

95

7-3653

45

.57

138

7-3654

60

.63

170

7-3656

60

.72

230

7-3658

60

.81

292

7-3662

80

1.02

442

7-3674

80

1.47

802

7-3686

80

1.63

1116

7-3700

110

1.98

1598

16 AWG – STRANDED

BASIC CAT. NO.

JACKET mils

O.D. in.

WEIGHT LBS/mft

7-3752

60

.60

135

7-3753

60

.65

178

7-3754

60

.70

214

7-3756

60

.80

307

7-3758

60

.90

399

7-3762

80

1.11

584

7-3774

80

1.51

1009

7-3786

110

1.82

1259

7-3800

110

2.10

2032