Type USE-2 or RHW-2 or RHH Building Wires 2kV

APPLICATIONS:
Where NEC jurisdiction applies; as Type RHW-2, 90 deg.C. in wet or dry locations, installed in air, conduit, or other recognized raceway. Sizes 1/0 and larger may be installed in cable tray per Article 318 of NEC. Otherwise, for general purpose applications at maximum conductor temperature of 90 deg.C. locations – including conduit, duct, tray trough, direct burial, and aerial installations.

CONSTRUCTION:
Stranded tinned or bare copper conductor, black XLP insulation, surface printed.

STANDARDS:

  • Conductors conform to ASTM B-3 & B-8 (& B-33 for tinned copper conductor).
  • RHW-2 Type ( 90 Deg.C. wet or dry) 2000 Volts per UL Standard 44.
  • Cables designed to pass the IEEE-383 ribbon burner flame test and UL 1277.
  • Jacket suitable for sunlight, oil & gasoline resistant applications I & II.
  • Cables meet requirements of ICEA S-95-658/NEMA WC70.

BASIC CAT. NO.

SIZE/AWG. KCMIL

STRD.

INSUL. mils

O.D.in.

AMPS 90° C

WEIGHT lbs/m ft.

5-204-2K 14 7 60 .195 25 30
5-205-2K 12 7 60 .215 30 40

5-206-2K

10

7

60

.240

40

55

5-207-2K

8

7

70

.290

55

75

5-208-2K

6

7

70

.330

75

110

5-209-2K

4

7

70

.380

95

160

5-210-2K

2

7

70

.430

130

245

5-211-2K

1

19

90

.510

150

315

5-212-2K

1/0

19

90

.550

170

390

5-213-2K

2/0

19

90

.600

195

480

5-214-2K

3/0

19

90

.650

225

595

5-215-2K

4/0

19

90

.700

260

735

5-216-2K

250

37

105

.780

290

875

5-217-2K

300

37

105

.830

320

1035

5-218-2K

350

37

105

.880

350

1200

5-219-2K

400

37

105

.930

380

1360

5-220-2K

500

37

105

1.01

430

1680

5-221-2K

600

61

120

1.12

475

2025

5-222-2K

750

61

120

1.22

535

2510

5-223-2K

1000

61

120

1.39

615

3250

5-224-2K

1250

91

140

1.54

665

4170

5-225-2K

1500

91

140

1.66

705

4960

5-226-2K 1750 91 140 1.77 735 5750
5-227-2K 2000 91 140 1.91 750 6560