Type SOOW Flexible Cords

APPLICATION:
Type SOOW flexible cords are permitted for use per Article 400 of the NEC in wiring for industrial machinery, motors and associated equipment, portable tools and equipment, and temporary electrical power and lighting installations for construction sites. Also suitable for indoor and outdoor use, for use in dry locations not to exceed min. -40 deg.C. or max. 90 deg.C., wet locations and other applicable locations; or when exposed to oil or coolant at temperatures not to exceed 60 deg.C. Ideal for flex applications in harsh environments where the highest degree of oil resistance and extended service life are essential.

CONSTRUCTION:
Flexible stranded copper conductors, heat, moisture and oil resistant EPR (Ethylene-Propylene-Rubber) insulated, color-coded* conductors cabled with fillers and a separator wrapped around the assembly to promote easier jacket removal, heat, moisture and oil resistant flexible CPE (Chlorinated Polyethylene) jacket overall, surface printed.

STANDARDS:

  • Copper conductors per ASTM B-3 & B-174.
  • Cables conform to UL-62, Flexible Cord and Fixture Wire.
  • Cables conform to requirements of Federal and Military Specification JC-580B.

BASIC CAT. NO.

SIZE/AWG

NO.OF CONDS.

STRAND

O.D. in.

COND.INSUL. mils

JKT. INSUL. mils

WEIGHT lbs/mft

11-1524

16

3

26/30

.39

30

60

95

11-1544

16

4

26/30

.42

30

60

115

11-1526

14

3

41/30

.54

45

80

170

11-1546

14

4

41/30

.58

45

80

205

11-1528

12

3

65/30

.60

45

95

225

11-1548

12

4

65/30

.65

45

95

270

11-1530

10

3

104/30

.66

45

95

290

11-1550

10

4

104/30

.72

45

95

355

11-1532

8

3

71/.015

.84

60

110

477

11-1552

8

4

71/.015

.93

60

125

616

11-1534

6

3

133/.0142

.98

60

125

670

11-1554

6

4

133/.0142

1.06

60

140

837

11-1536

4

3

133/.0179

1.14

60

140

956

11-1556

4

4

133/.0179

1.26

60

155

1225

11-1538

2

3

133/.0223

1.31

60

155

1310

11-1558

2

4

133/.0223

1.46

60

170

1712