Type PV or RHW-2 or RHH Building Wires 600V

APPLICATIONS:
Single conductor, sunlight resistant, direct burial, photovoltaic wire rated 90°C wet or dry,600V for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31(A) and other applicable parts of the National Electric Code (NEC),NFPA 70.

CONSTRUCTION:
Stranded bare copper conductor, black XLP insulation, surface printed.

STANDARDS:

  • Conductors conform to ASTM B-3 & B-8
  • RHW-2 (90°C wet/dry) or RHH (90°C dry)per UL
  • PV Type (90°C wet/dry) per UL4703.
  • Cables (1/0AWG and larger)designed to pass the IEEE-383, IEEE-1202/CSA FT-4 flame test.
  • Jacket suitable for sunlight resistant and direct burial applications.
  • Cables designed to pass UL 1581 VW-1 Flame Test
  • Meets cold bend and cold impact -40°C
  • Cables meet requirements of ICEA S-95-658/NEMA WC70.

BASIC CAT. NO.

SIZE/AWG. KCMIL

STRD.

INSUL. mils

O.D.in.

WEIGHT lbs/m ft.

5-504

14

7

60

.194

27

5-505

12

7

60

.214

36

5-506

10

7

60

.238

51

5-507

8

7

80

.313

88

5-508

6

7

80

.356

126

5-509

4

7

80

.405

183

5-510

2

7

80

.466

269

5-511

1

19

95

.515

333

5-512

1/0

19

95

.563

410

5-513

2/0

19

95

.608

502

5-514

3/0

19

95

.658

620

5-515

4/0

19

95

.714

767

5-516

250

37

110

.784

923

5-517

300

37

110

.837

1090

5-518

350

37

110

.887

1240

5-519

400

37

110

.932

1423

5-520

500

37

110

1.015

1718

5-521

600

61

125

1.122

2136

5-522

750

61

125

1.224

2597

5-523

1000

61

125

1.373

3411