Type PV or RHW-2 or RHH Building Wires 600V
DOWNLOADS | |
TYPE PV 600V Spec. Sheet |
APPLICATIONS:
Single conductor, sunlight resistant, direct burial, photovoltaic wire rated 90°C wet or dry,600V for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31(A) and other applicable parts of the National Electric Code (NEC),NFPA 70.
CONSTRUCTION:
Stranded bare copper conductor, black XLP insulation, surface printed.
STANDARDS:
- Conductors conform to ASTM B-3 & B-8
- RHW-2 (90°C wet/dry) or RHH (90°C dry)per UL
- PV Type (90°C wet/dry) per UL4703.
- Cables (1/0AWG and larger)designed to pass the IEEE-383, IEEE-1202/CSA FT-4 flame test.
- Jacket suitable for sunlight resistant and direct burial applications.
- Cables designed to pass UL 1581 VW-1 Flame Test
- Meets cold bend and cold impact -40°C
- Cables meet requirements of ICEA S-95-658/NEMA WC70.
BASIC CAT. NO. |
SIZE/AWG. KCMIL |
STRD. |
INSUL. mils |
O.D.in. |
WEIGHT lbs/m ft. |
---|---|---|---|---|---|
5-504 |
14 |
7 |
60 |
.194 |
27 |
5-505 |
12 |
7 |
60 |
.214 |
36 |
5-506 |
10 |
7 |
60 |
.238 |
51 |
5-507 |
8 |
7 |
80 |
.313 |
88 |
5-508 |
6 |
7 |
80 |
.356 |
126 |
5-509 |
4 |
7 |
80 |
.405 |
183 |
5-510 |
2 |
7 |
80 |
.466 |
269 |
5-511 |
1 |
19 |
95 |
.515 |
333 |
5-512 |
1/0 |
19 |
95 |
.563 |
410 |
5-513 |
2/0 |
19 |
95 |
.608 |
502 |
5-514 |
3/0 |
19 |
95 |
.658 |
620 |
5-515 |
4/0 |
19 |
95 |
.714 |
767 |
5-516 |
250 |
37 |
110 |
.784 |
923 |
5-517 |
300 |
37 |
110 |
.837 |
1090 |
5-518 |
350 |
37 |
110 |
.887 |
1240 |
5-519 |
400 |
37 |
110 |
.932 |
1423 |
5-520 |
500 |
37 |
110 |
1.015 |
1718 |
5-521 |
600 |
61 |
125 |
1.122 |
2136 |
5-522 |
750 |
61 |
125 |
1.224 |
2597 |
5-523 |
1000 |
61 |
125 |
1.373 |
3411 |