Type MC-IAC Interlocked Armor Power Cables Shielded 25-35kV

APPLICATIONS:
Where NEC jurisdiction applies; as Type MV-105 cable for installation aerially or in metal rack, tray, trough or cable trays, for power and control circuits not exceeding 25,000/35,000 volts at 133% and 100% insulation levels for 105 deg.C. continuous, 140 deg.C. emergency, and 250 deg.C. short-circuit operation in manufacturing and processing plants, substations and generating stations. When installed per NEC, cables meet the requirements of OSHA.

CONSTRUCTION:
Stranded copper conductors, semi-conducting layer, EPR insulation, semi-conducting layer, helically applied copper tape shield, conductors phase identified. Three conductors cabled together with a stranded copper grounding conductor in one interstice, suitable fillers, binder tape, aluminum or galvanized steel interlocked armor, PVC jacket overall, surface printed.

STANDARDS:

  • Conforms to AEIC CS8.
  • Type MV-105 MC cable per article 334 of the NEC.
  • Overall jacket suitable for Sunlight Resistant and Direct Buried applications.
  • Cables designed to pass the IEEE-383 ribbon burner flame test and are suitable “For CT Use.”
  • Cables conform to ICEA S-93-639 and ICEA S-97-682.

BASIC CAT. NO.

SIZE/AWG KCMIL

INSUL. THICK. mils

GROUND WIRE SIZE/AWG

O.D. in.

WEIGHT
lbs/m ft.

     

ALUM.
ARMOR

STEEL
ARMOR

9-4070-G

1/0

345

4

2.96

4162

4835

9-4071-G

2/0

345

4

3.04

4597

5289

9-4072-G

3/0

345

3

3.14

5102

5819

9-4073-G

4/0

345

3

3.28

5758

6506

9-4074-G

250

345

2

3.38

6292

7066

9-4075-G

350

345

2

3.60

7636

8465

9-4076-G

500

345

1

3.89

9639

10541