Type MC-IAC Interlocked Armor Power Cables 600 Volts

APPLICATIONS:
Where NEC jurisdiction applies; as Type MC cable, 90 deg.C. in wet or dry locations; for installation aerially, in conduit, cable trays, in underground ducts, with messenger or direct buried, for power and control circuits not exceeding 600 volts in manufacturing and processing plants, substations and generating stations. When installed per the NEC, cables meet requirements of OSHA. Permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC. Suitable for direct burial.

CONSTRUCTION:
Three-, or four conductors of stranded copper, XLP (Cross-Linked Polyethylene) insulated, phase-identified, conductors cabled with a stranded copper ground wire in one interstice, cable tape, aluminum or galvanized steel interlocked armor, black PVC (Polyvinyl Chloride) jacket overall, surface printed.

STANDARDS:

  • Conductors conform to ASTM B-3 & B-8.
  • Insulation conforms to UL Standard 44, and is approved as Type XHHW-2.
  • MC Type Cable per UL 1569.
  • Cables designed to pass the IEEE-383 ribbon burner flame test.
  • Cable suitable for Sunlight Resistant, Direct Buried and “For CT Use” applications.
  • Cables meet requirements of ICEA S-95-658.

To download the datasheet please click here

600 VOLT, THREE AND FOUR CONDUCTORS WITH GROUND, ARMORED

 

 

SIZE/AWG.
KCMIL

GRD.COND. SIZE/AWG

 
 

 
 

8

10

6

8

4

8

2

6

1

6

1/0

6

2/0

6

3/0

4

4/0

4

250

4

300

3

350

3

400

2

500

2

600

2

750

1

 

NO.OF CDRS

BASIC CAT.NO.

O.D. in.

WEIGHT lbs/mft

   

ALUM.
ARMOR

STEEL
ARMOR

 3

9-651-G

.850

410

500

3

9-652-G

.950

550

660

3

9-653-G

1.02

735

855

3

9-654-G

1.16

1080

1215

3

9-655-G

1.34

1310

1470

3

9-656-G

1.38

1575

1805

3

9-657-G

1.64

1885

2130

3

9-658-G

1.68

2315

2620

3

9-659-G

1.94

2820

3110

3

9-660-G

2.02

3360

3740

3

9-661-G

2.09

3900

4370

3

9-662-G

2.35

4490

4900

3

9-662-G4

2.36

5060

5670

3

9-663-G

2.59

6215

6700

3

9-664-G

2.79

7350

7860

3

9-665-G

2.97

9065

9655

 

NO.OF CDRS

BASIC CAT.NO.

O.D. in.

WEIGHT lbs/mft

   

ALUM.
ARMOR

STEEL
ARMOR

4

9-670-G

.910

500

590

4

9-671-G

1.02

685

800

4

9-672-G

1.11

955

1130

4

9-673-G

1.34

1360

1565

4

9-674-G

1.56

1680

1930

4

9-675-G

1.64

2000

2280

4

9-676-G

1.68

2420

2735

4

9-677-G

1.94

2995

3315

4

9-678-G

2.02

3605

4010

4

9-679-G

2.27

4320

4735

4

9-680-G

2.36

5200

5650

4

9-681-G

2.49

5950

6400

4

9-682-G

2.59

6570

7180

4

9-683-G

2.79

8045

8590

4

9-684-G

2.97

9520

10115

4

9-685-G

3.27

11825

12490