Type MC-IAC Instrumentation Cable


APPLICATIONS:
As multi-conductor Type MC cable, 90 deg.C. in dry locations, for installation indoors or outdoors, aerially or in a metal rack, trough, or cable trays; for control, lighting, power, and signal circuits not exceeding 600V. in manufacturing and processing plant and substations. May be used in NEC Class I and II, Division 2 and Class III, Division 1 and 2 hazardous locations. When installed per the NEC, cables meet the requirements of OSHA.

CONSTRUCTION:
Stranded copper conductors, XLP (Cross-Linked Polyethylene) insulated, Method 1 - Table E1 or E2 color-coded or Method 4 phase-identified conductors cabled with suitable fillers as necessary, cable tape, aluminum interlocked armor, black PVC (Polyvinyl Chloride) jacket overall, surface printed.

STANDARDS:

  • Conductors conform to ASTM B3 & B 8.
  • Insulation conforms to UL Standard 44.
  • UL Type MC cable 600 volts.
  • Overall jacket approved as Sunlight Resistant.
  • Cables designed to pass the IEEE-383 and IEEE-1202 tests.
  • Cables meet requirements of ICEA S-95-658/NEMA WC70.

18 AWG - STRANDED

BASIC CAT NO.

NO.OF CDRS

O.D.OVER ARMOR in.

O.D.OVER JKT in.

WEIGHT lbs/mft

9-0002

2

.430

.530

120

9-0003

3

.430

.530

130

9-0004

4

.430

.530

140

9-0005

5

.440

.540

155

9-0007

7

.520

.620

200

9-0009

9

.620

.720

250

9-0012

12

.670

.770

285

9-0019

19

.810

.910

415

9-0025

25

.850

.950

480

9-0037

37

1.01

1.11

620

16 AWG - STRANDED

BASIC CAT NO.

NO.OF CDRS

O.D.OVER ARMOR in.

O.D.OVER JKT in.

WEIGHT lbs/mft

9-0052

2

.430

.530

130

9-0053

3

.430

.530

145

9-0054

4

.440

.540

165

9-0055

5

.520

.620

195

9-0057

7

.560

.660

245

9-0059

9

.670

.770

330

9-0062

12

.710

.810

350

9-0069

19

.810

.910

510

9-0075

25

.950

1.05

605

9-0087

37

1.06

1.16

810