Type G-GC Portable Power Cables
APPLICATIONS:
Heavy duty portable cable for use with mobile mining equipment, such as shuttle cars, continuous miners, cutting or loading machines, conveyors, drills, pumps and submersible applications. For use in circuits not exceeding 2000 volts, maximum conductor temperature of 90 deg.C. For three-phase ac where grounding conductors and a fail-safe ground monitoring ground check conductor are required.
CONSTRUCTION:
Three insulated power conductors each consisting of flexible stranded copper, EPR (or TPR) insulation. Two insulated grounding conductors, each consisting of flexible stranded annealed copper, green insulation. One insulated ground check conductor consisting of flexible stranded annealed copper, yellow insulation. Three insulated power conductors cabled together, the ground check conductor placed in the valley, one grounding conductor in each of the other two valleys. Overall black CPE (Chlorinated Polyethylene) jacket.
STANDARDS:
- Conforms to ICEA S-75-381 Portable and Power Feeder.
BASIC CAT. NO. |
SIZE AWG KCMIL |
NO. OF STRDS |
INSUL.THICK. mills |
GRD. COND. SIZE AWG. |
GRD. CHECK SIZE AWG. |
O.D. in. |
WEIGHT lbs/mft |
---|---|---|---|---|---|---|---|
12-1109 |
6 |
133 |
60 |
10 |
10 |
1.05 |
735 |
12-1110 |
4 |
259 |
60 |
8 |
10 |
1.19 |
1065 |
12-1111 |
3 |
259 |
60 |
8 |
10 |
1.24 |
1245 |
12-1113 |
2 |
259 |
60 |
7 |
10 |
1.34 |
1480 |
12-1114 |
1 |
259 |
80 |
6 |
8 |
1.51 |
1885 |
12-1115 |
1/0 |
259 |
80 |
5 |
8 |
1.65 |
2290 |
12-1116 |
2/0 |
329 |
80 |
4 |
8 |
1.75 |
2710 |
12-1117 |
3/0 |
413 |
80 |
3 |
8 |
1.89 |
3270 |
12-1118 |
4/0 |
532 |
80 |
2 |
8 |
2.04 |
3975 |
12-1119 |
250 |
608 |
95 |
2 |
6 |
2.39 |
4950 |
12-1121 |
350 |
851 |
95 |
1/0 |
6 |
2.68 |
6625 |
12-1124 |
500 |
1221 |
95 |
2/0 |
6 |
3.03 |
8890 |