Type EPR Power Cables 5kV/8kV-1C

APPLICATION:
A- Where NEC jurisdiction applies; as 5000/8000 volts shielded power cable (133/100% insulation levels), Type MV-105, for use at conductor temperature not exceeding 105 deg.C. in wet or dry locations, when installed in accordance with the National Electrical Code.
B- Otherwise, for general purpose applications in wet or dry locations, in circuits not exceeding 5000 volts, phase to phase, at conductor temperatures not exceeding 105 deg.C. for normal, 130 deg.C. for emergency overload, and 250 deg.C. circuit conditions. Suitable for installation in conduit, trays, troughs, ducts, aerial, and direct burial applications.

CONSTRUCTION:
Stranded copper conductor, semi-conducting layer, EPR insulation, semi-conducting layer, helically applied copper tape shield, black PVC jacket overall, surface printed.

STANDARDS:

  • Conforms to AEIC CS8.
  • Type MV-105 power cable, 5,000/8,000 volts (133/100% insulation levels).
  • Overall jacket suitable for Sunlight Resistant and Direct Buried applications.
  • Sizes 1/0 AWG and larger designed to pass the IEEE-383 flame test and are suitable “For CT Use.”
  • Sizes 250 MCM and larger designed to pass the IEEE-1202 flame test.
  • Cables conform to ICEA S-93-639 and ICEA S-97-682.

                                 5000/8000 VOLTS, SHIELDED, 133/100% INSULATION LEVELS

BASIC CAT. NO.

SIZE AWG/KCMIL

NO. OF STRDS

INSUL. THICK. mills

JKT. THICK. mils

O.D. in.

WEIGHT lbs/mft

13-1005

8

7

115

60

.61

160

13-1006

6

7

115

60

.64

215

13-1007

4

7

115

60

.72

350

13-1008

2

7

115

60

.78

460

13-1009

1

19

115

60

.82

565

13-1010

1/0

19

115

60

.86

620

13-1011

2/0

19

115

80

.94

755

13-1012

3/0

19

115

80

.99

890

13-1013

4/0

19

115

80

1.05

1055

13-1014

250

37

115

80

1.10

1205

13-1016

350

37

115

80

1.21

1570

13-1018

500

37

115

80

1.36

2115

13-1021

750

61

115

80

1.54

2995

13-1022

1000

61

115

80

1.70

3870